Voltage Ratings
Test Voltage 70 KV
Rated Voltage 50 KV
Current Rating
Continuous (Amps RMS) 200 Amps
Maximum Interrupting Current (Amps) 4000
Specifications
Capacitor Discharge Decaying to 0 in 200 microseconds (kA) 100
Contact Resistance (Micro Ohms) 200
Contact Capacity (pF) 5.5
Contact Inductance (nH) 45
Mechanical Life (operations) 100,000
Auxiliary Contacts DPDT
Auxiliary Contact (Volts AC RMS) 230
Auxiliary Contact Current (Amps RMS) 15
Options (Model-Specific)
Contact Arrangement Normally Open
Insulator Length (in.) 6
Actuator (Volts) 100 VDC
Pull-in Current (Amps) 1.60 DC
Hold Current (Amps) 0.07 DC
Hold Power (Watts) 7.0
Time to Close (msec) 40
Break Time (msec) 100
Important Dimensions
Max Length 6.12 in / 155.45 mm
Max Width 5.37 in / 136.4 mm
Max Height 21.1 in / 535.94 mm
Weight 302 oz / 8.5616 kg